FACP Activations Appendix B: MS-9200
ACM-8RF PN 50362:C 03/21/01
35
Status functions of first 16 relays if the FACP has a UDACT-F installed.
Table 12 Status Relays (with UDACT-F)
MS-9200 Zone
ACM-8RF
Alarm Relay
ACM-8RF Trouble
Relay
SW3 Settings
System Status 1 System Alarm 5= System Trouble
1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF
System Status Relay 2 (not used) 6=Alarm Silence
System Status Relay 3 (not used) 7=Walk Test
System Status Relay 4 (not used) 8=Supervisory
System Status Relay 1 (not used) 5=NAC Fail
2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF
System Status Relay 2 (not used) Relay 6 (not used)
System Status Relay 3 (not used) 7=Battery Trouble
System Status Relay 4 (not used) 8=AC Fail